RF IS M18 nb-ST

Features/Options

  • Metal enclosure
  • M18 thread
  • Non-flush mounting
  • With M12 coupling, 4-pole
Note
  • 2 mounting nuts are included in delivery

Technical data

StandardsEN 60947-5-1
Enclosurebrass, nickeled
Front capPVC, black
Back capPVC, black
ConnectionCoupling M12 x 1, 4-pole
Cable length0.5 m, 1 m or 2 m
Degree of protectionIP 67 to IEC/EN 60529
Ambient temperature–25 °C … +70 °C
Rated operating isolation voltage Ui75 VDC
Rated operating current Ie0.2 mA
Rated operating voltage Ue3 … 5 VDC
Switching distancesn 8 mm; sa 0 … 6.48 mm;
sr 7.2 mm … 8.8 mm
Hysteresisapprox. 10 %
Repeatability< 5 %
Type of installationnon-flush
Switching frequencysee RF 96 ST / RF I/O
Correction factorsSteel (St37) = 1; V2A approx. 0.7;
Ms approx. 0.5; Al approx. 0.5;
Cu approx. 0.4
Actuatorsteel plate 24 x 24 x 1 mm, FE 360
NoteThe sensor may only be used in combination with RF 96 ST or RF I/O
Ordering details
Type code
Type   Material no.
RF IS M18 nb-ST 0.5 m 1261564
RF IS M18 nb-ST 1 m on request Produced to order.
RF IS M18 nb-ST 2 m 1189975